“A” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Acc1 to Acc2 frequency
transition point
A095
ACC CHfr
0000.0Hz
Output frequency at which
Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz
U
0.0
0.0
Hz
Acc1 to Acc2 frequency
transition point, 2nd motor
A295
2ACCCHfr
0000.0Hz
Output frequency at which
Accel1 switches to Accel2, 2nd
motor, range is 0.0 to 400.0 Hz
U
0.0
0.0
Hz
Dec1 to Dec2 frequency
transition point
A096
DEC CHfr
0000.0Hz
Output frequency at which
Decel1 switches to Decel2, range
is 0.0 to 400.0 Hz
U
0.0
0.0
Hz
Dec1 to Dec2 frequency
transition point, 2nd motor
A296
2DECCHfr
0000.0Hz
Output frequency at which
Decel1 switches to Decel2, 2nd
motor, range is 0.0 to 400.0 Hz
U
0.0
0.0
Hz
NOTE: For A095 and A096 (and for 2nd motor settings), if you set a very rapid Acc1 or
Dec1 time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or
Dec2 before reaching the target frequency. In that case, the inverter decreases the rate
of Acc1 or Dec1 in order to achieve the second ramp to the target frequency.