Network Communications Settings
The following table lists parameters that configure the inverter’s serial communications
port. The settings affect how the inverter communication with a digital operator (such
as SRW-0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to
“ModBus Network Communications” on page B-1
for more information on controlling
any monitoring your inverter from a network.
“C” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Selection of OPE / ModBus
C070
PARAM
REM
Two option codes:
02
}
OPE or option
03
}
ModBus (485)
U
02
02
Communication speed
selection
C071
COM BAU
4800
Three option codes:
04
}
4800 bps
05
}
9600 bps
06
}
19200 bps
U
06
04
baud
Node allocation
C072
COM ADR
00001
Set the address of the inverter on
the network. Range is 1 to 32
U
1.
1.
Communication parity
selection
C074
COM PRTY
NON
Three option codes:
00
}
No parity
01
}
Even parity
02
}
Odd parity
U
00
00
Communication stop bit
selection
C075
COM STP
1BIT
Range is 1 to 2
U
1
1
bit
Communication error select
C076
COM ESlct
None
Selects inverter response to
communications error.
Five options:
00
}
Trip (Error code E60)
01
}
Decelerate to a stop and trip
(Error code E60)
02
}
Disable
03
}
Free run stop (coasting)
04
}
Decelerate to a stop
U
02
02
Communication error time-
out
C077
COM ETIM
000.00s
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec
U
0.00
0.00
sec.
Communication wait time
C078
COM Wait
00000ms
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
U
0.
0.
msec.
3
60
Config
uri
ng Driv
e
Parameters
3
−
60