Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are presented in
the tables below.
Motor Output
Torque
Input
Voltage
kW
HP
Inverter Model
Power Terminal
Wiring Size
Range (AWG)
Ft-lbs
(N-m)
0.2
1/4
X200-002SFEF/NFU
0.4
1/2
X200-004SFEF/NFU
0.6
0.8
0.55
3/4
X200-005SFEF
0.75
1
X200-007SFEF/NFU
14
(75
q
C only)
1.1
1 1/2
X200-011SFEF
1.5
2
X200-015SFEF/NFU
12
2.2
3
X200-022SFEF/NFU
10
0.9
1.2
3.7
5
X200-037LFU
12
0.9
1.2
5.5
7 1/2
X200-055LFU
200V
Class
7.5
10
X200-075LFU
8
1.5
2.0
0.4
1/2
X200-004HFEF/HFU
0.75
1
X200-007HFEF/HFU
1.5
2
X200-015HFEF/HFU
16
(60
q
C only)
2.2
3
X200-022HFEF/HFU
3.0
4
X200-030HFEF
4.0
5
X200-040HFEF/HFU
14
(75
q
C only)
0.9
1.2
5.5
7 1/2
X200-055HFEF/HFU
400V
Class
7.5
10
X200-075HFEF/HFU
10
1.5
2.0
Torque
Terminal Connector
Wiring Size
Range (AWG)
Ft-lbs
(N-m)
Logic and Analog connectors
30 – 16
0.16 – 0.19
0.22 – 0.25
Relay connector
30 – 14
0.37 – 0.44
0.5 – 0.6
Wire Connectors
WARNING: Field wiring connections must be made by a UL Listed and CSA certified
ring lug terminal connector sized for the wire gauge being used. The connector must be
fixed using the crimping tool specified by the connector manufacturer.
Terminal (ring lug)
Cable support
Cable
xiv
xiv