External Signal for DC Braking
When the terminal
[
DB
]
is turned ON, the
DC braking feature is enabled. Set the
following parameters when the external DC
braking terminal
[
DB
]
is to be used
:
x
A053 – DC braking delay time setting.
The range is 0.1 to 5.0 seconds.
x
A054 – DC braking force setting. The
range is 0 to 100%.
The scenarios to the right help show how DC
braking works in various situations.
1. Scenario 1 – The
[
FW
]
or
[
RV
]
terminal is
ON. When
[
DB
]
is ON, DC braking is
applied. When
[
DB
]
is OFF again, the
output frequency ramps to the prior level.
2. Scenario 2 – The Run command is applied
from the operator keypad. When the
[
DB
]
terminal is ON, DC braking is applied.
When the
[
DB
]
terminal is OFF again, the
inverter output remains OFF.
3. Scenario 3 – The Run command is applied
from the operator keypad. When the
[
DB
]
terminal is ON, DC braking is applied
after the delay time set by A053 expires.
The motor is in a free
-
running
(
coasting
)
condition. When the
[
DB
]
terminal is OFF
again, the inverter output remains OFF.
Option
Code
Terminal
Symbol
Function Name
State
Description
ON
Applies DC injection braking during deceleration
07
DB
External DC
Braking
OFF
Does not apply DC injection braking during
deceleration
Valid for inputs
:
C001~C005
Required settings
A053, A054
Notes
:
x
Do not use the
[
DB
]
input continuously or for a
long time when the DC braking force setting
A054 is high
(
depends on the motor application
)
.
x
Do not use the
[
DB
]
feature for continuous or
high duty cycle as a holding brake. The
[
DB
]
input is designed to improve stopping
performance. Use a mechanical brake for
holding a stop position.
Example (requires input configuration—see
page 3–49
):
See I/O specs on
page 4–6.
5
4
3
2
1
L
PCS P24
DB
[FW,RV]
1
0
[DB]
1
0
Output
frequency
Scenario 1
t
Run command
from operator
1
0
[DB]
1
0
Output
frequency
Scenario 2
t
Run command
from operator
1
0
[DB]
1
0
Output
frequency
Scenario 3
t
delay
A053
4
15
Operations and
Monitori
ng
4
−
15
Operations and
Monitoring