Analog Input Current/Voltage Select
The
[
AT
]
terminal selects whether the inverter uses the voltage
[
O
]
or current
[
OI
]
input terminals for external frequency control. When intelligent input
[
AT
]
is ON, you
can set the output frequency by applying a current input signal at
[
OI
]-[
L
]
. When the
[
AT
]
input is OFF, you can apply a voltage input signal at
[
O
]-[
L
]
to set the output
frequency. Note that you must also set parameter A001 = 01 to enable the analog
terminal set for controlling the inverter frequency.
Option
Code
Terminal
Symbol
Function Name
State
Description
ON
16
AT
Analog Input
Voltage/Current
Select
OFF
See the table down below
Valid for inputs
:
C001~C005
Required settings
A001 = 01
Notes
:
x
If the
[
AT
]
option is not assigned to any
intelligent input terminal, then inverter
recognizes
[
AT
]
= OFF in following table.
Combination of A005 setting and
[
AT
]
input
for analog input activation.
x
Be sure to set the frequency source setting
A001=01 to select the analog input terminals.
Example (default input configuration shown
for –FU models; –FE models require input
configuration—see
page 3–49
):
See I/O specs on
page 4–6.
NOTE
:
You cannot use both the
[
O
]
and
[
OI
]
inputs at the same time on the X200
inverter.
5
4
3
2
1
L
PCS P24
AT
AM H
O OI
L
Å
+ -
4-20 mA
0-10 V
4
22
Operations and
Monitori
ng
A005
[
AT
]
Input
Analog Input Configuration
ON
Keypad Pot
02
OFF
[
O
]
ON
Keypad Pot
03
OFF
[
OI
]
04
(
ignored
)
[
O
]
05
(
ignored
)
[
OI
]
4
−
22
Operations and
Monitoring