Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when
it is in Run Mode. The output logic is
active low, and is the open collector type
(switch to ground).
Option
Code
Terminal
Symbol
Function Name
State
Description
ON
when inverter is in Run Mode
00
RUN
Run Signal
OFF
when inverter is in Stop Mode
Valid for inputs:
11, AL0 – AL2
Required settings
(none)
Notes:
x
The inverter outputs the [RUN] signal
whenever the inverter output exceeds the start
frequency specified by parameter B082
. The
start frequency is the initial inverter output
frequency when it turns ON.
x
The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the
coil from damaging the inverter’s output
transistor.
Example for terminal [11] (default output
configuration shown – see
page 3-54
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
page 4-35 and 3-54
):
See I/O specs on
page 4-6
RY
Inverter output
terminal circuit
CM2
11
RUN
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
RUN
[FW,RV]
1
0
Output
frequency
t
Run
signal
1
0
start freq.
B082
ON
4
39
Operations and
Monitori
ng
4
−
39
Operations and
Monitoring