Configuring the Inverter for Multiple Motors
Simultaneous Connections
For some applications, you may need to connect two or
more motors (wired in parallel) to a single inverter’s
output. For example, this is common in conveyor
applications where two separate conveyors need to
have approximately the same speed. The use of two
motors may be less expensive than making the
mechanical link for one motor to drive multiple
conveyors.
Some of the characteristics of using multiple motors
with one drive are:
x
The inverter output must be rated to handle the
sum of the currents from the motors.
x
You must use separate thermal protection switches
or devices to protect each motor. Locate the device
for each motor inside the motor housing or as close
to it as possible.
x
The wiring for the motors must be permanently
connected in parallel (do not remove one motor
from the circuit during operation).
NOTE: The motor speeds are identical only in theory. That is because slight differences
in their loads will cause one motor to slip a little more than another, even if the motors
are identical. Therefore, do not use this technique for multi-axis machinery that must
maintain a fixed position reference between its axes.
Inverter Configuration for Two Motor Types
Some equipment manufacturers may have a single type of machine that has to support
two different motor types—and only one motor will be connected at a time. For example,
an OEM may sell basically the same machine to the US market and the European
market. Some reasons why the OEM needs two motor profiles are:
x
The inverter power input voltage is different for these markets.
x
The required motor type is also different for each destination.
In other cases, the inverter needs two profiles because the machine characteristics vary
according to these situations:
x
Sometimes the motor load is very light and can move fast. Other times the motor
load is heavy and must move slower. Using two profiles allows the motor speed,
acceleration and deceleration to be optimal for the load and avoid inverter trip (fault)
events.
x
Sometimes the slower version of the machine does not have special braking options,
but a higher performance version does have braking features.
Motor 1
Motor 2
U/T1
V/T2
W/T3
U/T1
V/T2
W/T3
to Nth motor
X200
4
60