List of Holding Registers
Network Data
Func.
Code
Name
R/W
Description
Reg.
Range
Res.
A020
Multi-speed 0 setting
R/W Defines the first speed of a
multi-speed profile, range is 0.0 /
start frequency to 400 Hz
A020 = Speed 0 (1st motor)
1029h
0 / start
freq. to
4000
0.1 Hz
A220
Multi-speed 0 setting
2nd motor
R/W Defines the first speed of a
multi-speed profile, range is 0.0 /
start frequency to 400 Hz
A220 = Speed 0 (2nd motor)
150Fh
0 / start
freq. to
4000
0.1 Hz
A021
Multi-speed 1 setting
R/W
102Bh
A022
Multi-speed 2 setting
R/W
102Dh
A023
Multi-speed 3 setting
R/W
102Fh
A024
Multi-speed 4 setting
R/W
1031h
A025
Multi-speed 5 setting
R/W
1033h
A026
Multi-speed 6 setting
R/W
1035h
A027
Multi-speed 7 setting
R/W
1037h
A028
Multi-speed 8 setting
R/W
1039h
A029
Multi-speed 9 setting
R/W
103Bh
A030
Multi-speed 10 setting
R/W
103Dh
A031
Multi-speed 11 setting
R/W
103Fh
A032
Multi-speed 12 setting
R/W
1041h
A033
Multi-speed 13 setting
R/W
1043h
A034
Multi-speed 14 setting
R/W
1045h
A035
Multi-speed 15 setting
R/W
Defines 15 more speeds,
range is 0.0 / start frequency to
400 Hz.
A021= Speed 1...
A035 = Speed 15
1047h
0 / start
freq. to
4000
0.1 Hz
A038
Jog frequency setting
R/W Defines limited speed for jog,
range is 0.00 / start frequency
to 9.99 Hz
1048h
0 / start
freq. to
999
0.01 Hz
A039
Jog stop mode
R/W
Define how end of jog stops
the motor; three options:
00...Free-run stop
01...Controlled deceleration
02...DC braking to stop
1049h
0, 1, 2
A041
Torque boost select
R/W
104Ah
A241
Torque boost select,
2nd motor
R/W
Two options:
00...Manual torque boost
01...Automatic torque boost
1510h
0, 1
A042
Manual torque boost
value
R/W
104Bh
A242
Manual torque boost
value, 2nd motor
R/W
Can boost starting torque
between 0 and 20% above normal
V/f curve,
range is 0.0 to 20.0%
1511h
0 to 200
0.1 %
A043
Manual torque boost
frequency adjustment
R/W
104Ch
A243
Manual torque boost
frequency adjustment,
2nd motor
R/W
Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%
1512h
0 to 500
0.1 %
A044
V/f characteristic curve
selection
R/W
104Dh
A244
V/f characteristic curve
selection, 2nd motor
R/W
Two available V/f curves;
two select codes:
00...Constant torque
01...Reduced torque
06...Reduced torque1
1513h
0, 1, 6
A045
V/f gain setting
R/W
104Eh
A245
V/f gain setting, 2nd
motor
R/W
Sets voltage gain of the inverter,
range is 20. to 100.%
1514h
20 to 100
1 %
B
26
Appe
ndix B
B
−
26
Appendix B