List of Holding Registers
Network Data
Func.
Code
Name
R/W
Description
Reg.
Range
Res.
B052
OV-LAD Stop level of
non stop operation
setting
R/W Setting the OV-LAD stop level of
non stop operation. Range is 0.0
to 1000.0
10CBh
0 to 10000
0.1 V
B053
Deceleration time of
non stop operation
setting
R/W Range is 0.1 to 3000
10CCh
1 to 30000
0.1 sec
B054
Frequency width of
quick deceleration
setting
R/W Setting of the first quick
deceleration width. Range is 0.0
to 10.0
10CEh
0 to 100
0.1 Hz
B055
DC bus AVR P-gain
R/W Proportional gain adjustment for
DC bus AVR function. Range is:
0.2 to 5.0
1173h
2 to 50
0.1
B056
DC bus AVR I-time
R/W Integration time adjustment for
DC bus AVR function. Range is:
0.0 to 150.0
1174h
0 to 1500
0.1s
B080
[AM]analog signal gain R/W Adjust of analog output at
terminal [AM],
range is 0 to 255
10CFh
0 to 255
B082
Start frequency
adjustment
R/W Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
10D1h
5 to 99
0.1 Hz
B083
Carrier frequency
setting
R/W Sets the PWM carrier (internal
switching frequency), range is
2.0 to 12.0 kHz
10D2h
20 to 120
0.1 Hz
B084
Initialization mode
(parameters or trip
history)
R/W Select the type of initialization to
occur, three option codes:
00
}
Trip history clear
01
}
Parameter initialization
02
}
Trip history clear and
parameter initialization
10D3h
0, 1, 2
B085
Country for
initialization
R/W Select default parameter values
for country on initialization,
three option codes:
00
}
Japan
01
}
Europe
02
}
US
10D4h
B
33
B
−
33
Appendix B