Standard Functions
NOTE:. Mark “
9
” in B031=10 shows the accessible parameters when B031 is set “10”,
high level access.
“A” Group Parameters
Default Setting
Func.
Code
Name
-FE
(EU)
-FU
(USA)
B031
=10
User
Setting
A001
Frequency source setting
01
00
U
A201
Frequency source setting, 2nd motor
01
00
U
A002
Run command source setting
01
02
U
A202
Run command source setting, 2nd motor
01
02
U
A003
Base frequency setting
50.0
60.0
U
A203
Base frequency setting, 2nd motor
50.0
60.0
U
A004
Maximum frequency setting
50.0
60.0
U
A204
Maximum frequency setting, 2nd motor
50.0
60.0
U
A005
[AT] selection
02
02
9
A011
Pot./O-L input active range start
frequency
0.0
0.0
9
A012
Pot./O-L input active range end
frequency
0.0
0.0
9
A013
Pot./O-L input active range start voltage
0.
0.
9
A014
Pot./O-L input active range end voltage
100.
100.
9
A015
Pot./O-L input start frequency enable
01
01
9
A016
External frequency filter time constant
8.
8.
9
A020
Multi-speed 0 setting
0.0
0.0
9
A220
Multi-speed 0 setting, 2nd motor
0.0
0.0
9
A021
Multi-speed 1 setting
0.0
0.0
9
A022
Multi-speed 2 setting
0.0
0.0
9
A023
Multi-speed 3 setting
0.0
0.0
9
A024
Multi-speed 4 setting
0.0
0.0
9
A025
Multi-speed 5 setting
0.0
0.0
9
A026
Multi-speed 6 setting
0.0
0.0
9
A027
Multi-speed 7 setting
0.0
0.0
9
A028
Multi-speed 8 setting
0.0
0.0
9
A029
Multi-speed 9 setting
0.0
0.0
9
A030
Multi-speed 10 setting
0.0
0.0
9
A031
Multi-speed 11 setting
0.0
0.0
9
A032
Multi-speed 12 setting
0.0
0.0
9
A033
Multi-speed 13 setting
0.0
0.0
9
A034
Multi-speed 14 setting
0.0
0.0
9
A035
Multi-speed 15 setting
0.0
0.0
9
A038
Jog frequency setting
1.00
1.00
9
A039
Jog stop mode
00
00
9
A041
Torque boost select
00
00
U
A241
Torque boost select, 2
nd
motor
00
00
U
A042
Manual torque boost value
1.8
1.8
9
A242
Manual torque boost value, 2
nd
motor
0.0
0.0
9
C
3
Appe
ndix C
C
−
3
Appendix C