“A” Group Parameters
Default Setting
Func.
Code
Name
-FE
(EU)
-FU
(USA)
B031
=10
User
Setting
A043
Manual torque boost frequency
adjustment
10.0
10.0
9
A243
Manual torque boost frequency
adjustment, 2nd motor
0.0
0.0
9
A044
V/f characteristic curve selection
00
00
U
A244
V/f characteristic curve selection,
2nd motor
00
00
U
A045
V/f gain setting
100.
100.
9
A245
V/f gain setting, 2nd motor
100.
100.
9
A051
DC braking enable
00
00
9
A052
DC braking frequency setting
0.5
0.5
9
A053
DC braking wait time
0.0
0.0
9
A054
DC braking force for deceleration
0.
0.
9
A055
DC braking time for deceleration
0.0
0.0
9
A056
DC braking / edge or level detection for
[DB] input
01
01
9
A061
Frequency upper limit setting
0.0
0.0
9
A261
Frequency upper limit setting, 2nd
motor
0.0
0.0
9
A062
Frequency lower limit setting
0.0
0.0
9
A262
Frequency lower limit setting, 2nd
motor
0.0
0.0
9
A063,
A065,
A067
Jump (center) frequency setting
0.0
0.0
0.0
0.0
0.0
0.0
9
A064,
A066,
A068
Jump (hysteresis) frequency width
setting
0.5
0.5
0.5
0.5
0.5
0.5
9
A071
PID enable
00
00
9
A072
PID proportional gain
1.0
1.0
9
A073
PID integral time constant
1.0
1.0
9
A074
PID derivative time constant
0.0
0.0
9
A075
PV scale conversion
1.00
1.00
9
A076
PV source setting
00
00
9
A077
Reverse PID action
00
00
9
A078
PID output limit
0.0
0.0
9
A081
AVR function select
00
00
U
A082
AVR voltage select
230/400
230/460
U
A085
Operation mode selection
00
00
U
A086
Energy saving mode tuning
50.0
50.0
U
A092
Acceleration (2) time setting
15.00
15.00
9
A292
Acceleration (2) time setting, 2nd motor
15.00
15.00
9
A093
Deceleration (2) time setting
15.00
15.00
9
A293
Deceleration (2) time setting, 2nd motor
15.00
15.00
9
C
4
Appe
ndix C
C
−
4
Appendix C