CAUTION: In all the instrumentations in this manual, covers and safety devices are occasionally
removed to describe the details. While operating the product, make sure that the covers and
safety devices are placed as they were specified originally and operate it according to the
instruction manual.
CAUTION: Do not discard the inverter with household waste.
Contact an industrial waste management company in your area who can
treat industrial waste without polling the environment.
UL
Cautions, Warnings and Instructions
xii
Warnings and Cautions for Troubleshooting and Maintenance
The warnings and instructions in this section summarizes the procedures necessary to ensure an
inverter installation complies with Underwriters Laboratories
£
guidelines.
WARNING: “USE 60/75
q
C Cu wire only” or equivalent. For models X200-005S, -007S,
-011S, -022S, -007N, -015N, -015L, -022L, -037L, -055L, -075L.
WARNING: “USE 75
q
C Cu wire only” or equivalent. For models X200-002S, -004S, -002N, -004N,
-002L, -004L, -007L, -022H, -030H, -037H, -040H, -055H, 075H.
WARNING: “USE 60
q
C Cu wire only” or equivalent. For models X200-004H, -007H, and –015H.
WARNING: “Open Type Equipment”
WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 240V maximum when protected by Class CC, G, J or R fuses or circuit
breaker having an interrupting rating not les than 100,000 rms symmetrical amperes, 240 volts
maximum”. For models with suffix S, N or L.
WARNING: “Suitable for use on a circuit capable of delivering not more than 100k rms
symmetrical amperes, 480V maximum when protected by Class CC, G, J or R fuses or circuit
breaker having an interrupting rating not les than 100,000 rms symmetrical amperes, 480 volts
maximum.” For models with suffix H.
WARNING: “Install device inn pollution degree 2 environment.”
WARNING: “Maximum Surrounding Air Temperature 50
q
C”. or equivalent.
WARNING: “Caution-Risk of electric shock
capacitor discharge time is at least 5 minutes.”
WARNING: “Solid state motor overload protection is provided in each model”.
WARNING: “Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the National Electric
Code and any additional local codes” or equivalent.
xiii
xiii