Two Stage Acceleration and Deceleration
When terminal
[
2CH
]
is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings
(
F002
and F003
)
to use the second set of
acceleration/ deceleration values. When the
terminal is turned OFF, the inverter is
returned to the original acceleration and
deceleration time
(
F002 acceleration time 1,
and F003 deceleration time 1
)
. Use A092
(
acceleration time 2
)
and A0093
(
deceleration
time 2
)
to set the second stage acceleration
and deceleration times.
In the graph shown above, the
[
2CH
]
becomes active during the initial acceleration.
This causes the inverter to switch from using acceleration 1
(
F002
)
to acceleration 2
(
A092
)
.
Option
Code
Terminal
Symbol
Function Name
State
Description
ON
Frequency output uses 2nd
-
stage acceleration and
deceleration values
09
2CH
Two
-
stage Accelera
-
tion and Deceleration
OFF
Frequency output uses the initial acceleration 1
and deceleration 1 values
Valid for inputs
:
C001~C005
Required settings
A092, A093, A094=00
Notes
:
x
Function A094 selects the method for second
stage acceleration. It must be set = 00 to select
the input terminal method in order for the
[
2CH
]
terminal assignment to operate.
Example (default input configuration shown—see
page 3–49
):
See I/O specs on
page 4–6.
5
4
3
2
1
L
PCS P24
2CH
- FU models
[2CH]
1
0
Output
frequency
t
[FW,RV]
1
0
Target
frequency
initial
second
4
17
Operations and
Monitori
ng
4
−
17
Operations and
Monitoring