Intelligent Terminal Functions
“C” Group Parameters
Default Setting
Func.
Code
Name
-FE
(EU)
-FU
(USA)
B031
=10
User
Setting
C001
Terminal [1] function
00
00
U
C201
Terminal [1] function, 2nd motor
00
00
U
C002
Terminal [2] function
01
01
U
C202
Terminal [2] function, 2nd motor
01
01
U
C003
Terminal [3] function
02
16
U
C203
Terminal [3] function, 2nd motor
02
16
U
C004
Terminal [4] function
03
13
U
C204
Terminal [4] function, 2nd motor
03
13
U
C005
Terminal [5] function
18
18
U
C205
Terminal [5] function, 2nd motor
18
18
U
C011
Terminal [1] active state
00
00
U
C012
Terminal [2] active state
00
00
U
C013
Terminal [3] active state
00
00
U
C014
Terminal [4] active state
00
01
U
C015
Terminal [5] active state
00
00
U
C021
Terminal [11] function
01
01
U
C026
Alarm relay terminal function
05
05
U
C028
[AM] signal selection
00
00
9
C031
Terminal [11] active state
00
00
U
C036
Alarm relay active state
01
01
U
C038
Output mode of low load detection
signal
01
01
9
C039
Low load detection level
Rated current for
each inverter model
9
C041
Overload level setting
Rated current for
each inverter model
9
C241
Overload level setting, 2nd motor
Rated current for
each inverter model
9
C042
Frequency arrival setting for
acceleration
0.0
0.0
9
C043
Frequency arrival setting for
deceleration
0.0
0.0
9
C044
PID deviation level setting
3.0
3.0
9
C052
PID FBV function high limit
100.0
100.0
9
C053
PID FBV function variable low limit
0.0
0.0
9
C070
Selection of OPE / ModBus
02
02
9
C071
Communication speed selection
06
04
9
C072
Node allocation
1.
1.
9
C074
Communication parity selection
00
00
9
C075
Communication stop bit selection
1
1
9
C076
Communication error select
02
02
9
C077
Communication error time-out
0.00
0.00
9
C078
Communication wait time
0.
0.
9
C081
O input span calibration
100.0
100.0
9
C082
OI input span calibration
100.0
100.0
9
C
8
Appe
ndix C
C
−
8
Appendix C