5.4
WIRING SIZE AND MINIMUM REQUIREMENTS OF THE PROTECTION DEVICES
!
C A U T I O N
•
Check to ensure that the field supplied electrical components
(mains power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical
data indicated on this chapter and they comply with national and local
codes. If it is necessary, contact with your local authority in regards to
standards, rules, regulations, etc.
• Use a dedicated power circuit for the indoor unit. Do not use a power
circuit shared with the outdoor unit or any other appliance.
?
N O T E
• Electric fuses can be used instead of magnetic Circuit Breakers (CB).
In that case, select fuses with similar rated values as the CB.
• The Earth Leakage Breaker (ELB) mentioned on this manual is also
commonly known as Residual Current Device (RCD) or Residual
Current Circuit Breaker (RCCB).
• The Circuit Breakers (CB) are also known as Thermal-Magnetic
Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Use wires which are not lighter than the polychloroprene
sheathed flexible cord (code designation 60245 IEC 57).
Outdoor unit
Model
Power supply
Max.
current
(A)
Power supply cables
Transmitting
cables
CB
(A)
ELB
(nº of poles/A/mA)
EN60335-1
EN60335-1
RAS-4WHVNPE
1~ 230V 50Hz
20
2 x 4.0 mm² + GND
2 x 0.75 mm
2
20
2/40/30
RAS-5WHVNPE
25
2 x 6.0 mm² + GND
25
RAS-6WHVNPE
25
2 x 6.0 mm² + GND
25
RAS-4WHNPE
3N~ 400V 50Hz
14
4 x 2.5 mm² + GND
15
4/40/30
RAS-5WHNPE
14
4 x 2.5 mm² + GND
15
RAS-6WHNPE
16
4 x 4.0 mm² + GND
20
Indoor unit alone
Model
Power
supply
Operation mode
Max.
current
(A)
Power supply
cables
Transmitting
cables
CB
(A)
ELB
(nº of
poles/A/
mA)
EN60335-1
EN60335-1
RWH-4.0VNFE
1~
230V
50Hz
Without simultaneous operation
of electric heater in DHW tank
24
2 x 6.0 mm² + GND
2 x 0.75 mm
2
32
2/40/30
With simultaneous operation of
electric heater in DHW tank
38
2 x 10.0 mm² + GND
40
RWH-5.0VNFE
Without simultaneous operation
of electric heater in DHW tank
28
2 x 6.0 mm² + GND
32
With simultaneous operation of
electric heater in DHW tank
42
2 x 10.0 mm² + GND
50
2/63/30
RWH-6.0VNFE
Without simultaneous operation
of electric heater in DHW tank
31
2 x 6.0 mm² + GND
32
2/40/30
With simultaneous operation of
electric heater in DHW tank
45
2 x 10.0 mm² + GND
50
2/63/30
RWH-4.0NFE
3N~
400V
50Hz
Without simultaneous operation
of electric heater in DHW tank
10
4 x 2.5 mm² + GND
15
4/40/30
With simultaneous operation of
electric heater in DHW tank
24
2 x 4.0 mm² + GND
25
RWH-5.0NFE
Without simultaneous operation
of electric heater in DHW tank
10
4 x 2.5 mm² + GND
15
With simultaneous operation of
electric heater in DHW tank
24
2 x 4.0 mm² + GND
25
RWH-6.0NFE
Without simultaneous operation
of electric heater in DHW tank
10
4 x 2.5 mm² + GND
15
With simultaneous operation of
electric heater in DHW tank
24
2 x 4.0 mm² + GND
25
?
N O T E
The data corresponding to DHW tank heater is calculated in combination with the YUTAKI S80 domestic hot water tank accessory “DHWT-(200/300)
S-3.0H2E”.