ENGLISH
Indoor unit in combination with DHW tank
Model
Power
supply
Operation mode
Max.
current
(A)
Power supply
cables
Transmitting
cables
CB
(A)
ELB
(nº of
poles/A/mA)
EN60335-1
EN60335-1
RWH-4.0VNFWE
1~ 230V
50Hz
Without simultaneous operation of
electric heater in DHW tank
24
2 x 6.0 mm² + GND
2 x 0.75 mm
2
32
2/40/30
With simultaneous operation of
electric heater in DHW tank
36
2 x 10.0 mm² + GND
40
RWH-5.0VNFWE
Without simultaneous operation of
electric heater in DHW tank
27
2 x 6.0 mm² + GND
32
With simultaneous operation of
electric heater in DHW tank
40
2 x 10.0 mm² + GND
50
2/63/30
RWH-6.0VNFWE
Without simultaneous operation of
electric heater in DHW tank
31
2 x 6.0 mm² + GND
32
2/40/30
With simultaneous operation of
electric heater in DHW tank
43
2 x 10.0 mm² + GND
50
2/63/30
RWH-4.0NFWE
3N~ 400V
50Hz
Without simultaneous operation of
electric heater in DHW tank
10
4 x 2.5 mm² + GND
15
4/40/30
With simultaneous operation of
electric heater in DHW tank
22
4 x 4.0 mm² + GND
25
RWH-5.0NFWE
Without simultaneous operation of
electric heater in DHW tank
10
4 x 2.5 mm² + GND
15
With simultaneous operation of
electric heater in DHW tank
22
4 x 4.0 mm² + GND
25
RWH-6.0NFWE
Without simultaneous operation of
electric heater in DHW tank
10
4 x 2.5 mm² + GND
15
With simultaneous operation of
electric heater in DHW tank
22
4 x 4.0 mm² + GND
25
?
N O T E
• The data corresponding to “
With simultaneous operation of electric heater in DHW tank
” is calculated in combination with the YUTAKI S80 DHWT
accessory “DHWS(200/260)S-2.7H2E”.
• The data corresponding to “Without simultaneous operation of electric heater in DHW tank” does not consider the consumption of simultaneous
operation of the electric heater in the domestic hot water tank (DSW4-3 set in OFF).
• The DHW tank heater is intended to be used in case that indoor and/or outdoor unit are out of order. If the heater operation of the DHW tank is
enabled during the indoor unit operation, the indoor unit CB and ELB may trip-OF. If it is desired to enable the DHW tank heater operation during
normal indoor unit operation, adjust de DSW4 pin 3 of the PCB1 in “ON” position and consider the recommended protections detailed in the data “
With simultaneous operation of electric heater in DHW tank).
!
C A U T I O N
•
Ensure specifically that there is an Earth Leakage Breaker (ELB) installed for the units (outdoor and indoor unit).
• If the installation is already equipped with an Earth Leakage Breaker (ELB), ensure that its rated current is large enough to hold the current of the
units (outdoor and indoor unit).
ELECTRICAL AND CONTROL SETTINGS
PMML0340B rev.1 - 03/2016
17