1. Introduction
This section provides information on the minimum installation requirements for ATSC E-
Compact Series transmitters with recommendations on shelter, tower, antennas, cables,
grounding, mains, transient preventions, etc.
2. Minimum Requirements
2.1. AC Mains - Wire Gauge
The following details the consumption with the equipment running at its maximum power.
Current (A) on each wire:
The current values specified in the table are according to the load of each phase, which
will determine the size of the conductors and protection.
Said gauge is the minimum recommended for the transmitter in question, if the cable
length is longer, consider a voltage drop in the cable maximum of 5%.
The section of the neutral conductor should be the same as the phase.
The section of the ground conductor must be the same as the conductor’s phase.
AC load for infrastructure install (A) - E-Compact Series - ATSC
MODEL
M110
M220 / B220
T220
T380
(A)
Wire Gauge
(A)
Wire Gauge
(A)
Wire Gauge
(A)
Typical
Wire Gauge
mm²
AWG
mm²
AWG
mm²
AWG
mm²
AWG
EC702MP-BB3
8.6
4.17
11
5.0
3.31
12
EC704MP-BB3*
14.3
6.63
9
8.2
4.17
11
Not available or uncommonly used
*EC704MP-BB3
operates on M110 electrical network using two PSUs.
M110
M220
B220
T220
T380
110VAC ±15%
Between Phase and
Neutral
220VAC ±15%
Between Phase B
(Wild Leg) and
Neutral
220VAC ±15%
Between 2-Phases
220VAC ±15%
Between 3-Phases.
380VAC ±15%
Between 3 Phases
220VAC ±15%
Between each
Phases and Neutral
Summary of Contents for EC702MP-BB3
Page 68: ...68 108 E Compact MP BB3 Series VGS Carrier Software Version 1 75 1 70 1 71 1 78 ...
Page 84: ...84 108 E Compact MP BB3 Series B220 BIPHASIC 220VAC 2 PHASE 110VAC GND ...
Page 85: ...85 108 E Compact MP BB3 Series M220 SINGLEPHASE 220VAC 1 PHASE NEUTRAL GND ...
Page 106: ...106 108 E Compact MP BB3 Series Section 8 Attachments ...
Page 108: ...108 108 E Compact MP BB3 Series ...