Chapter 6 Communication mode
6 - 85
Hi
-P
ro
to
col
Error in Hi-Protocol mode
The detected error in Hi-Protocol operation will be indicated in high byte of WX us2 and 3. (The operation will
continue if the error level is not serious.) If the next task code is received properly, the error code WX us2 and 3
will be cleared.
If the TRNS command is executed with some missoperation in Hi-Protocol mode, the return code of TRNS 9
command will be “Illegal command specifying error (Error code H50)”.
Table 6.24 Hi-Protocol mode error during operation
No.
Error
Code
name
Error
level
Detail contents
1
HFF
CPU error
---
EH-SIO operation has been stopped due to the error detection of
CPU module (L.RES ON) was done.
2
---
Watch dog timer
Error
Fatal
Failure
MPU of EH-SIO can’t operate according the system program
anymore, EH-SIO has detected watch dog timer error of MPU.
3
H03
OS system error
Fatal
Failure
EH-SIO has detected an error of system OS.
4
H50
Non-valid command
error
Warning
TRNS 9 command has been used for the port specified as
SLAVE function or easy data link function.
5
H8A
Parity error
Warning
Parity error has been detected in the received data by EH-SIO.
6
H8B
Framing error
Warning
Framing error has been detected in the received data by EH-SIO.
7
H8C
Over run error
Warning
Over run error has been detected in the received data by EH-SIO.
8
H8D
Check code error
Warning
Check code error has been detected in the received data by
EH-SIO.
9
H8E
Receiving timeout error
Warning
EH-SIO could not complete the receive operation within the
specified time.
10
H8F
Sending timeout error
Warning
EH-SIO could not complete the send operation within the
specified time. (the monitoring time interval is fixed and it is not
possible to change this time interval.)
11
H91
Receiving
illegal message
Warning
EH-SIO receives message data including illegal data.
« Note »
EH-SIO is checking parity error and framing error in every byte. In case of Hi-Protocol mode, since only the
newest error is indicated, “parity error” and “framing error” can be overwritten by newest error such as “chek code
error”. So, if the “check code error” is detected, check also transmit character structure and transmit speed.
Summary of Contents for EH-150 Series
Page 2: ......
Page 10: ...M E M O ...
Page 30: ...Chapter 4 Installation 4 10 M E M O ...
Page 156: ...Chapter 7 System setup 7 12 M E M O ...
Page 164: ...Chapter 8 Daily and Periodic Inspection 8 8 M E M O ...