Chapter 4 Installation
4 - 6
4.3.2
Connection of RS-422 / 485 interface
The port 1 and 2 can select a communication interface. When you use RS-422 or RS-485 interface, please set up
with a communication setting switch. In addition, RS-422 or RS-485 interface is decided by connection of signal.
Table 4.6 RS-422 / 485 Signal (Port1)
Terminal layout
No.
Signal
Signal Name
Diagram of internal circuit
1
SG
Ground for signal
2
N.C.
(Not used)
3
N.C.
(Not used)
4
SD
+
Send data +
5
SD
-
Send data –
6
RD
-
Receive data –
7
RD
+
Receive data +
8
N.C.
(Not used)
Signal name and Connector pin arrangement (Port1)
Table 4.7 Signal name (EH-SIO side) and connector pin arrangement ( Port1 / RS-422/485)
Pin
No.
Signal Name
Symbol
Signal Direction
Specifications
EH-SIO
External device
1
Ground for signal
SG
Ground for signal
2
(Not used)
N.C.
--
--
Not used
3
(Not used)
N.C.
--
--
Not used
4
Send data +
SD
+
Data send from EH-SIO.
5
Send data –
SD
-
Data send from EH-SIO.
6
Receive data –
RD
-
Data received from external device.
7
Receive data +
RD
+
Data received from external device.
8
(Not used)
N.C.
--
--
Not used
8
1
.
..
.
M
icro
P
ro
ce
ss
o
r
1) SG
4) SD
+
5) SD
-
7) RD
+
6) RD
-
+
- +
-
Summary of Contents for EH-150 Series
Page 2: ......
Page 10: ...M E M O ...
Page 30: ...Chapter 4 Installation 4 10 M E M O ...
Page 156: ...Chapter 7 System setup 7 12 M E M O ...
Page 164: ...Chapter 8 Daily and Periodic Inspection 8 8 M E M O ...