Chapter 5 Control of EH-SIO
5 - 4
[2] Command timeout time
Set the timeout time of TRNS 9 command.
H0000 : command timeout disable
H0000 : command timeout enable. (Setting value x 10 ms)
If EH-SIO does not receive data within the configured time, TRNS 9 is cancelled as command timeout error.
Max. timeout time is 655,350 ms(HFFFF).
[3] Top I/O address of sending data area
Set the top I/O address of sending data area.
The method to specify the data area is different according to used CPU.
EH-CPU:
EHV-CPU:
Reference : Two "timeouts"
"Timeout" exists in TRNS 9 command and EH-SIO each other. The "command timeout" is for CPU module
configured in s parameter. The "receiving timeout" is for EH-SIO configured in initial setting. The purpose of
each timeout is different.
If a command timeout error occurs, CPU module will close TRNS 9 command while EH-SIO is still working. In
this case, EH-SIO does not receive the new command from CPU module. The command timeout time should be
larger value than the receiving timeout time. (If command timeout error occurs, please initialize TRNS 9
command.)
EH-SIO
EH-CPU
EHV-CPU
TRNS 9
External device
Command timeout
Receiving timeout
EHV-CPU
S+9
ADRIO command
Setting by ADR command
EH-CPU
S+9
Type
:
WR
H000A
WL
H000B
WM
H000C
I/O No.
:
H0000
~
HFFFF