Chapter 5 Configuration of Communication parameters
5.2
Configuration of Ethernet parameters using EH-ETH2 Configurator
Communication parameters are configured or confirmed via EH-ETH2 Configurator.
Table 5.2
The list of the items can be configured by EH-ETH2 Configurator
Items Section
number to refer
(1) Ethernet parameters
IP address of self station
Configuration of destination for diagnostic
Configuration of task code port
Section 5.2.7
(2) ASR parameters
ASR General Information
ASR connection setting
ASR I/O Area setting
Section 5.4.1 to 3
(3) Downloading/Uploading of setup file
Section 5.4.4
(4) Other
Information of firmware version
[Reset Module] button
Section 5.2.6
5.2.1 Setting
procedure
Figure 5.1 shows the outline of setting procedure.
Connect PC and EH-ETH2 with LAN
cable and HUB.
Confirm the network setting of PC
After changing the dip switch on
EH-ETH2, power on PLC.
Open EH-ETH2 Configurator on PC.
Set Communication Parameters
After changing the dip switch on
EH-ETH2, reset EH-ETH2.
Finish setting
Configuration mode
Normal operation mode
*1: Please install EH-ETH2 Configurator beforehand.
The Internet access is required for installation of EH-ETH2 Configurator.
Start Setting
(*1)
Figure 5.1
The outline of setting procedure
5-2