Chapter 6 Task code communication
- Setting of LADDER EDITOR for Windows®
(1) Open LADDER EDITOR for Windows® and go off-line mode.
(2) Choose [Environment Set] in [Utility] menu in the offline mode.
(3) Choose [Communication]dialog box.
A) Communication type
: Ethernet
B) Host name
: EH-ETH2 (Name in Hosts file )
C) Port number
: 3004
After setting, click [OK] button.
A)
B)
C)
(4)Choose [GRS] in [File] menu.
All setting are completed with this process.
After this, LADDER EDITOR for Windows® can communicate via EH-ETH2 in [Online] or [on-direct]
Caution
After setting Ethernet connection, it takes about 45 seconds to display “Communication Error” message in
the following cases. This time period is due to Windows internal processing.
(1) To try to go [online] or [on-direct] when the setting of EH-ETH2 is not correct, or to try to go [online]
or [on-direct] when the setting of PC or LADDER EDITOR for Windows® is not correct,.
(2) To try to go [online] or [on-direct] to EH-ETH2 without the power.
(3) Power off EH-ETH2 during communication.
(4) To Change I/O assignment during communication.
(5) EH-ETH2 breaks down during communication.
(6) To disconnect LAN cable during communication or breaking the cable.
6-8