Chapter 3 Programming
3 – 8
Configure I/O modules according to the list below.
Model names
Device Names
EH-XD8, 16
EH-XA16, H16
16 Digital input
EH-XD32, 32E, 32H
32 Digital input
EH-XD64 64
Digital
input
EH-YR8B, 12, 16
EH-YT8, 16
EH-YTP8, 16, 16S
EH-YS4, 16
16 Digital output
EH-YT32, 32E, 32H
EH-YTP32, 32E
32 Digital output
EH-YT64
EH-YTP64
64 Digital output
EH-PT4 4
Analog
input
EH-AX44, 8V, 8H, 8I, 8IO
EH-AXH8M
EH-TC8
8 Analog input
EH-AY22, 2H, 4V, 4H, 4I *1
EH-AYH8M
8 Analog output
EH-CU, CUE
EH-CU/E
EH-POS EH-POS/4
EH-RMP EH-RMP
EH-SIO EH-SIO
*
1 Although the number of channel is not 8, configure “8 ch. Analog output”.
3.3.2 Scan For Devices
Instead of plugging I/O modules one by one, actual information can be read out from connected CPU.
Right click on basic or expansion base and choose “Scan For Devices...”. Then “Scan Devices” dialog appears. Click
“Copy all devices to project”. This function works for chosen base only. If you have several expansion bases, repeat
“Scan For Device” for each base.
N o t e
“Scan For Devices” works only when logout, however, gateway and active path must be set accordingly.