Chapter 2 Specifications
2 – 37
(19) EH-YR16
Specification
EH-YR16
Output specification
Relay output
Number of outputs
16
Rated load voltage
100/240V AC, 24V DC
Minimum switching current
1mA (5V DC), except after a great current switching
Leak current
None
1 circuit
2A
Maximum load
current
1 common
8A (Ambient temperature 40
°
C), see the following derating table
OFF
Î
ON 10ms
maximum
Output
response time
ON
Î
OFF 10ms
maximum
Insulation system
Relay insulation
Output display
Green LED
External connection
Removal type screw terminal block (M3)
Number of output points / commons
16 (1 common, 2 terminals)
Surge removal circuit
None
Fuse
None
External power supply
Not used
Internal current consumption (5V DC)
430 mA maximum
Terminal configuration
No.
Signal
name
Diagram of Internal circuit
[1] 0
[2] 1
[3] 2
[4] 3
[5] 4
[6] 5
[7] 6
[8] 7
[9] C
[10] 8
[11] 9
[12] 10
[13] 11
[14] 12
[15] 13
[16] 14
[17] 15
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
Screw for
fixing
[18] C
LED
Internal
circuit
0
C
15
EH-YR16 Derating table
Ma
xim
um comm
on cu
rr
en
t (
A
)
8
7
6
5
4
3
2
1
0
20 30 40 50 55
Ambient temperature (
°
C)