Chapter 2 Specifications
2 – 61
Setting switch
Support to analog data and digital data
Switch
No.
Setup Function
1
2
Input range setting for ch.0 to 3
OFF
OFF
0 to 10 V DC
ON
OFF
-10 to +10 V DC
OFF
ON
0 to 22 mA
1, 2
ON
ON
4 to 22 mA
3
4
Input range setting for ch.4 to 7
OFF
OFF
0 to 10 V DC
ON
OFF
-10 to 10 V DC
OFF
ON
0 to 22 mA
3, 4
ON
ON
4 to 22 mA
5 Input
filter
OFF
Enable
5
ON Disable
6 Resolution
OFF
1/16384 (14 bits)
6
ON
1mV or 0.002mA
7 (System
mode)
7
OFF
Always OFF (Do not turn ON
)
8 (System
mode)
8
OFF
Always OFF (Do not turn ON)
Current / Voltage switch
Switch
No.
Setup Function
1 to 8
1 to 4 5 to 8
Select current or voltage
OFF
OFF
voltage input for ch.0 to 7
ON
OFF
current input for ch.0 to 3
voltage input for ch.4 to 7
OFF
ON
voltage input for ch.0 to 3
current input for ch.4 to 7
ON
ON
current input for ch.0 to 7
[Highlighted part is factory default setting.]
Note) Be sure to set dip switches before use. The dip switches must be set while power off, otherwise setting status is not updated.
When the input range is changed, be sure to set current / voltage switch accordingly.
5 10
V
3FFFH(16383)
2710H(10000)
0
1FFFH(8191)
1388H(5000)
Resolution 1/16384
Resolution 1mV
0 to 10 V DC
-10 to +10 V DC
4 to 22 mA
0 to 22 mA
10 22
mA
0
3FFFH(16383)
2AF8H(11000)
1FFFH(8191)
1388H(5000)
Resolution 1/16384
20
3A2EH(14894)
2710H(10000)
Resolution 0.002mA
10
22
mA
0
4
3FFFH(16383)
2328H(9000)
1174H(4468)
0FA0H(3000)
F830H(-2000)
0H(0)
Resolution 1/16384
Resolution 0.002mA
38E3H(14563)
20
1F40H(8000)
-10
V
0
1FFFH(8191)
2710H(10000)
E000H(-8192)
D8F0H(-10000)
(2’s complement)
0000H(0)
Resolution 1mV
+10
Resolution 1/16384