Chapter 2 Specifications
2 – 80
2.9.4 PROFIBUS-DP master module : EH-RMP
Module features
Type (Weight)
EH-RMP (Approx. 0.13kg (0.28Ib.))
Dimensions
(mm (in.))
Connector 1
DIP switch
Reset switch
Termination switch
Connector 2
30 (1.18)
100 (3.
9
4)
95 (3.74)
Name Description
Connector 1
Connect to PC (configurator), 9pin male Sub-D
Be careful, this connector become hot.
Reset switch
When module is abnormal, module is reset by pushing this.
Switch No.
4 3
Supplementary explanation
(when the CPU is stopped)
OFF
OFF
CLEAR mode: the output data is cleared.
OFF
ON
FREEZE mode: the output data is frozen.
ON
OFF
COPY mode: the output data is coped from the CPU.
DIP switch
*1
(No. 1,2 not used)
ON ON
Not
use
Termination switch
ON: bus termination enabled
OFF: bus termination disabled
Connector 2
Connect to field bus, 9pin female Sub-D
The screw is the terminal for functional earth.
*1: For setting of this switch, remove the module from the rack. If the setting ends, cover with the protection sheet.
LED name
Front view
LED name
Description
Color
STATUS
The state of the EH-RMP
Green
RUN Communication
running
Green
ERR
Error on communication line
Red
RDY
Device has no error
Green
PROFIBUS
EH-RMP
RDY
ERR
RUN
TOKEN
STATUS
TOKEN
Lit all the time
Green