Warning:
Verify the storage system is powered off normally and in idle mode
before turning off the PDU circuit breakers. Otherwise, turning off the PDU
circuit breakers can leave the storage system in an abnormal condition.
Table 22 Maximum idle power per chassis
Chassis
Maximum idle power [VA]
Controller Chassis 0 or 1
500
SFF Drive Chassis
1,120
LFF Drive Chassis
720
FMD Drive Chassis
1,280
Normal power on/off procedures
This section provides general information about turning on and off the power
to the storage system. If further assistance is required, contact customer
support.
Power on procedures
Before you begin
• Confirm the storage system is in idle mode. See
Note:
The control panel includes a safety feature to prevent the storage
system power from being turned on or off accidentally. The PS power ON/OFF
switch does not work unless the ENABLE switch is moved to and held in the
ENABLE position while the power switch is moved to the ON or OFF position.
Perform the procedure to turn on the storage system. If applicable, refer to
the figure of the control panel in
Figure 32 Storage system control panel on
.
Procedure
1.
On the control panel, check the amber BS LED and make sure it is lit. It
indicates that the storage system is in idle mode.
2.
In the PS area on the control panel, move the ENABLE switch to the
ENABLE position and hold it there. While holding the switch in the
ENABLE position, move the PS ON/OFF switch to the ON position. Then
release both switches.
3.
Wait for the storage system to complete its power-on self-test and boot
up processes. Depending on the storage system configuration, this can
take several minutes.
The storage system will not go to the READY state until the cache backup
batteries are charged to at least 50%. This can take 90 minutes if the
110
Power on/off procedures
Hitachi Virtual Storage Platform G1000, G1500, and Virtual Storage Platform F1500 Hardware Guide