Specific considerations of combinability
Outdoor unit
Combinability
Minimum
nominal
combination
capacity
(HP)
Nominal
combination
capacity
(HP)
Maximum
nominal
combination
capacity
(HP)
Minimum
combination
quantity of
indoor units
Minimum
capacity of
the combined
indoor units
(HP)
Maximum
quantity of
combined
indoor units
(The sum of
the installed
RPK and all
other indoor
units)
RPK restrictions
Maximum number
of combinable RPK
indoor units
(This number of units
is the sum of the
installed RPK-FSN3M
and RPK-FSNH3M with
its expansion valve kit
EV-1.5N1)
RAS-4FS(V)N(Y)3E
2.0
4.0
5.2
1
0.6 (*)
8
6
RAS-5FS(V)N(Y)3E
2.5
5.0
6.5
1
0.6 (*)
10
7
RAS-6FS(V)N(Y)3E
3.0
6.0
7.8
1
0.6 (*)
12
7
(*): Indoor unit of 0.8HP set as 0.6HP by DSW setting only for Set Free Mini Series 3.
Maximum refrigerant piping length
(m)
Item
4HP
(5/6)HP
Maximum length from the outdoor unit to the furthest
indoor unit (L1)
Actual length
≤ 75
Equivalent length
≤ 95
Maximum length from the 1st multikit to the furthest indoor unit (L2)
≤ 40
Maximum length between multikit and indoor unit (L3)
Case a) Header branch
≤ 15
Case b) Line branch
≤ 10
Maximum height difference between outdoor and indoor
unit (Hi-O)
If the outdoor unit is higher than the indoor unit
≤ 30
If the outdoor unit is lower than the indoor unit
≤ 30
Maximum height difference between each indoor unit (H1)
≤ 15
Maximum height difference between multikit and indoor unit (H2)
≤ 5
Total piping length (L1+L3
1
+L3
2
+...+L3
n-1
)
≤ 125
≤ 135
Choice of each multikit
Case a) Header branch
MH-84AN (4 branches)
MH-108AN (8 branches)
Case b) Line branch
E-102SN3
•
Considerations by maximum quantity of combined indoor units
All the following points should be taken in consideration when the quantity of indoor units is over the value shown in the following
table:
Outdoor unit
Quantity of combined indoor units
RAS-4FS(V)N(Y)3E
> 6
RAS-5FS(V)N(Y)3E
> 8
RAS-6FS(V)N(Y)3E
> 9
REFRIGERANT PIPING & REFRIGERANT CHARGE
PMML0354A rev.1 - 03/2015
14