13.4.2 Wire size
Connection wiring
Recomended minimum sizes for field provided wires:
Model
Power supply
Max. current (A)
Power source cable size
Transmitting cable size
EN60 335-1
EN60 335-1
All Indoor Units
1~ 230V 50Hz
5.0
0.75 mm²
0.75 mm²
RAS-4FSVN3E
26.0
6.0 mm
2
RAS-5FSVN3E
26.0
6.0 mm²
RAS-6FSVN3E
26.0
6.0 mm²
RAS-4FSNY3E
3N~ 400V 50Hz
13.0
4.0 mm²
RAS-5FSNY3E
13.0
4.0 mm²
RAS-6FSNY3E
13.0
4.0 mm²
?
N O T E
•
Follow local codes and regulations when selecting field wires, Circuit breakers and Earth Leakage breakers
•
Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord (code designation H05RN-F)
Main switch protection
Select the main switches in according to the next table:
Model
Power source
Max. Current
(A)
CB
(A)
ELB
(no. poles/A/mA)
All Indoor Units
1~ 230V 50Hz
5.0
6
2/40/30
RAS-4FSVN3E
26.0
32
RAS-5FSVN3E
26.0
32
RAS-6FSVN3E
26.0
32
RAS-4FSNY3E
3N~ 400V 50Hz
13.0
20
4/40/30
RAS-5FSNY3E
13.0
20
RAS-6FSNY3E
13.0
20
ELB: Earth leakage breaker; CB: Circuit breaker
ELECTRICAL WIRING
PMML0354A rev.1 - 03/2015