Code
number
Category
Abnormality
Cause
48
Inverter
Activation of overcurrent protection activation for
inverter
Failure of DIP-IPM, heat exchanger clogged, locked
compressor, EVI/EVO failure or overcharge.
51
Abnormality of current sensor for inverter
Failure of control PCB, inverter module.
53
Protection activation of inverter module
Inverter module abnormality.
Failure of compressor, clogging of heat exchanger.
54
Inverter fin temperature increase
Abnormal inverter fin thermistor, clogging of heat exchanger,
abnormal outdoor fan.
55
Inverter module abnormality
Failure of inverter module.
57
Outdoor fan
Fan motor abnormality
Disconnected wire of incorrect wiring between control PCB and
inverter PCB.
Incorrect wiring or fan motor abnormality.
b1
Indoor unit
number setting
Incorrect setting of the unit and the refrigerant
cycle number.
Over 64 indoor units setting by number or indoor unit address.
b5
Incorrect indoor unit connection number setting
There are more than 17 units not corresponding to H-Link II
connected to one system
EE
Compressor
Compressor protection
Failure of compressor.