38
5-2-3 Con nection of Th er m al Over load Rela y wit h CT
Wh en CT side is V-conn ect ed, 2 set of CT can m ak e 3-ph ase pr ot ection . Th en, in order t o ensu re corr ect oper a t ion ,
m ak e wir in g a s sh own in F ig. 33 a n d F ig. 34 by pa yin g a tt en t ion t o t h e m oun t in g dir ect ion a nd polar it y.
F ig. 33 Con nection dia gr a m F ig. 34 Mou nt in g of CT a n d wir in g
A cu rr en t flows to t h e 3 hea t ers of t h e t herm a l over loa d r ela y a t 3-ph ase overloa d.
F ig. 35
E ven if ph a se fa ilur e occu r s, cur r ent flows t o t h e 2 h eat ers wit h ou t pha se fa ilur e, rega r dless of t h e in ser t ion ph ase of
CT; t h e sam e oper at ion is m a de as t h e 3-ph ase t herm a l over load r ela y n ot usin g CT.
F ig. 36
Wh er e 3set s of CT ar e u sed, in dividu a l CT's ar e con nect ed t o t h e r espect ive hea t er s of t h e t h er ma l over loa d r ela y as
sh own in Fig. 37 a n d F ig. 38.
Th en , even if t he CT pola r it ies a r e a r r a n ged u n ifor m ly, prot ect ion ca n be ensu r ed.
Summary of Contents for H100C
Page 2: ......
Page 9: ...5 Fig 1 H35 Horizontal Plunger type Fig 2 H300C Link structure ...
Page 36: ...32 Fig 28 ...