Offset (1)
Description
Values
Read/Write
22
Unit operation condition
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
Read
23
(Not used)
(Not used)
(Not used)
24
Ambient temperature (2)
-63ºC ~ 63ºC
Read
25
Remote control switch temperature
(only when available in the unit) (2)
-63ºC ~ 63ºC
Read
26
Remote control switch configuration
b0: 0 Master/1Slave
b1: 0 wih RCS/1 Without RCS
Read/Write
27
Remote control switch group
0: No group
1~255
Read/Write
28~30
(Not used)
(Not used)
(Not used)
31
Remote sensor temperature (2)
-63ºC ~ 63ºC
Read
?
N O T E
• (1) Register address is calculated as: “N + (Address * 32) + Offset” where:
• N: Data table position is 2000, position 20000 is also available to maintain compatibility with old Modbus gateway.
• Address: Indoor unit address as configured by configuration software.
• (2) These numbers refer to signed 16-bit value using 2-complement format for negative values
• (3) Bit 0 (ON/OFF) and Bit 4 (Louver) selectable only when all centrals are actived.
• In order to full lock setting from RCS (Central shown in RCS) set this register to 31.
OPERATION
PMML0351A rev.4 - 04/2020
10