Offset
Description
Values
Read/Write
Availability
VRF
RAC
ATW
55
Control Circuit 1: Water heating Fix
Setting Temp
0~80
Read/Write
O
56
Control Circuit 1: Water cooling Fix
Setting Temp
0~80
Read/Write
O
57
Control Circuit 1: Eco mode
0: ECO
Read/Write
O
1: Comfort
58
Control Circuit 1: Heat ECO Offset
Temperature
1~10
Read/Write
O
59
Control Circuit 1: Cool ECO Offset
Temperature
1~10
Read/Write
O
60
Control Circuit 1: External MBS/KNX
Thermostat Available
0: Not Available
Read/Write
O
1: Available
61
Control Zone 1: Thermostat Setting
0~65535
Read/Write
O
62
Control Zone 1: Room Ambient Tem-
perature
-32667~32667
Read/Write
O
63
Control Circuit 2 Run/Stop
0: Stop
Read/Write
O
1: Run
64
Control Heat. OTC Zone 2
0: No
Read/Write
O
1: Points
2: Gradient
3: Fix
65
Control Cool. OTC Zone 2
0: No
Read/Write
O
1: Points
2: Fix
66
Control Circuit 2: Water heating Fix
Setting Temp
0~80
Read/Write
O
67
Control Circuit 2: Water cooling Fix
Setting Temp
0~80
Read/Write
O
68
Control Circuit 2: Eco mode
0: ECO
Read/Write
O
1: Comfort
69
Control Circuit 2: Heat ECO Offset
Temperature
1~10
Read/Write
O
70
Control Circuit 2: Cool ECO Offset
Temperature
1~10
Read/Write
O
71
Control Circuit 2: External MBS/KNX
Thermostat Available
0: Not Available
Read/Write
O
1: Available
72
Control Zone 2: Thermostat Setting
0~65535
Read/Write
O
73
Control Zone 2: Room Ambient Tem-
perature
-32667~32667
Read/Write
O
74
Control DHWT Run/Stop
0: Stop
Read/Write
O
1: Run
75
Control DHWT Setting Temperature
0~80
Read/Write
O
76
Control DHW Boost
0: No request
Read/Write
O
1: Request
77
Reserved
78
Control DHW Demand Mode
0: Standard
Read/Write
O
1: High demand
79
Control Swiming Pool Run/Stop
0: Stop
Read/Write
O
1: Run
80
Control Swiming Pool Setting Tempe-
rature
0~80
Read/Write
O
81
Control AntiLegionella Run/Stop
0: Stop
Read/Write
O
1: Run
ENGLISH
OPERATION
PMML0351A rev.4 - 04/2020
13