Offset
Description
Values
Read/Write
Availability
VRF
RAC
ATW
140
System Configuration
b0: Zone 1 Heating
Available
Read
O
b1: Zone 2 Heating
Available
b2: Zone 1 Cooling
Available
b3: Zone 2 Cooling
Available
b4: DHWT Available
b5: SWP Available
b6: Room thermostat
available Zone 1
b7: Room thermostat
available Zone 2
b8: Wireless Setting C1
b9: Wireless Setting C2
b10: Wireless Room
Temperature C1
b11: Wireless Room
Temperature C2
b12: Slave Unit
141
Operation State
0: OFF
Read
O
1: Cool Demand –OFF
2: Cool Thermo-OFF
3: Cool Thermo-ON
4: Heat Demand-OFF
5: Heat Thermo-OFF
6: Heat Thermo-ON
7: DHW-OFF
8: DHW-ON
9: SWP-OFF
10: SWP-ON
11: Alarm
142
Outdoor Ambient Tº
-80~100
Read
O
(Outdoor ambient temperature)
143
Water Inlet Tº
-80~100
Read
O
(Water Inlet unit temperature)
144
Water outlet Tº
-80~100
Read
O
(Water outlet unit temperature)
145
H-Link Communication State
0: No alarm
Read
O
1: There is no commu-
nication with RCS or
Yutaki unit during more
than 180 seconds
2: Data initialization
146
Software PCB
Read
O
147
Software LCD
Read
O
148
Unit Capacity
Read
O
149
Unit Power Consumption
Read
O
150
Water Outler HP (TwoHP)
0~100 Only for Yutaki S
& S Combi
Read
O
151
Ta1av: Outdoor Unit Ambient Average
Temperature
-80~100
Read
O