Offset
Beskrivelse
Værdier
Læs/Skriv
Availability
VRF
RAC-
ATW
17
Ventilator status
0: Low
Læs
O
O
1: Medium
2: High
3: High2
4: Auto
18
Setting temperature status
ºC (set according to the
unit working range)
Læs
O
O
19
Temperature setting with 0.5°C
intervals status
ºC x10 (19.5ºC read as
195)
Læs
O
20
Heating temperature setting for AUTO
Cool/Heat status
°C
Læs
O
21
Heating Temperature setting for AUTO
Cool/heat with 0.5°C intervals status
ºC x 10 (19.5ºC read as
195)
Læs
O
22
Cooling Temperature setting for AUTO
Cool/heat status
°C
Læs
O
23
Cooling Temperature setting for AUTO
Cool/heat with 0.5°C intervals status
ºC x 10 (19.5ºC read as
195)
Læs
O
24
Spjæld status
0 ~ 7 (7 is Auto)
Læs
O
25
Air inlet temperature reading
-63ºC ~ 63ºC
Læs
O
26
Air outlet temperature reading
-63ºC ~ 63ºC
Læs
O
27
Gas pipe temperature reading
-63ºC ~ 63ºC
Læs
O
28
Liquid pipe temperature reading
-63ºC ~ 63ºC
Læs
O
29
Alarmkode
Alarmenhed fra 7-delt
Læs
O
O(1)
30
Årsag til kompressorstop
(Læs
servicevejledningen)
Læs
O
31
Indendørsenhed
ekspansionsventilåbning
0~100
Læs
O
32
Enhedens driftstilstand
0: OFF
Læs
O
O
1: Thermo OFF
2: Thermo ON
3: Alarm
33
Remote temperature sensor (THM4)
value
-63ºC ~ 63ºC
Læs
O
34
Remote control switch temperature
(only when available in the unit)
-63ºC ~ 63ºC
Læs
O
O
35
Remote control switch configuration
b0: 0 Master/1Slave
Læs/Skriv
O
b1: 0 wih RCS/1 Without
RCS
36
Fjernbetjeningsgruppe
0: No group
Læs/Skriv
O
1~255
37
CN3 Configuration status
b0: Input 1 open/close
Læs
O
b1: Input 2 open/close
b2: Enabled/Disabled
(Indicates if the unit has
CN3 enabled with any
function)
38~49
Reserveret
DRIFT
PMML0351A rev.4 - 04/2020
142