Chapter 6 Slave Controller Specifications
6-3
6.3
Settings of Node Address/Baud Rate
The node addresses and baud rate should be set as follows.
Table 6.3 Node Address/Baud Rate setting
Node address
NA1
NA2
NA4
NA8 NA16 NA32
0
OFF OFF OFF OFF OFF OFF
1
ON
OFF OFF OFF OFF OFF
2 OFF
ON
OFF OFF OFF OFF
...
...
...
...
...
...
...
62 OFF
ON
ON
ON
ON
ON
63
ON
ON
ON
ON
ON
ON
Baud Rate
DR0
DR1
125 kbps
OFF
OFF
250 kbps
ON
OFF
500 kbps
OFF
ON
NA32
NA16
NA8
NA4
MA2
NA1
DR1
DR0
→
ON
Setting prohibited
ON ON
When setting the DIP switches, turn off the power supply of the PLC and disconnect the module from the
network. The setting isn't reflected until the module is reset.
Set the baud rate in such a way that all the devices on the network communicate at the same speed.
Set the node addresses for the other devices in such a way that they do not overlap.
6.4
Setting of Output Status
The output status is set by the DIP switches on the side of the module.
This status specifies whether to clear or hold the output data to the output module in case of a communication
error or when the EH-CPU stops.
Bits 1, 2, and 3 are reserved by the system. They must always be set to OFF.
Table 6.4 Output Status setting
Output
status
Bit 4
Bit 3
Bit2
Bit1
Clear OFF OFF OFF OFF
ON 4 3 2 1
→
Hold
ON
6.5 Communication
Connector
Table 6.5 Communication connector terminal arrangement
Terminal layout
Number
Signal
Wire color
5 V+
Red
4 CAN_H White
3 Drain Bare
wire
2 CAN_L Blue
5
1
4
3
2
1 V- Black
Default
Default
Default