Chapter 8 Starting Up
8-2
S T E P
1 Setup on the PLC side
1. Perform the I/O assignment.
Start up the LADDER EDITOR for Windows® and assign the I/O assignment of EH-RMD.
I/O assignment of "CPU link" is for EH-RMD link mode, "Remote 2" is for EH-RMD remote mode..
2. Set the CPU link parameters.(LINK mode only)
Click the link No. to be used. Next, set the transmission area.
Top assign No. should be fixed to WL0/WL1000.
(*1)
Please set Last assign No. according to the following table.
*1: Top Assign No. of No.1 Link is WL0, and Top Assign No. of No.2 Link is WL1000.
Last Assign No. setting
EH-RMD
Last Assign No.
SOFTWARE
VER. 00
1 to FF
(1000 to 10FF)
SOFTWARE
VER. 01
or later
1FF Fixed
(11FF Fixed)
After downloading I/O assignment to CPU module, check the indication of "STATUS" LED on the
EH-RMD.
Link mode : Solid Green
Remote mode : Solid Green or 4 times flash Green
In case of remote mode, after scan list is configured in RMDCFG, it is
necessary to assign Remote stations again.
After downloading I/O assignment CPU module, close Ladder Editor for Windows® or enter off-line mode
(GRS).