Chapter 13 Mounting and Wiring
13-3
13.4 How to Prepare Communication Cables
Prepare the communication cables according to the procedure below and attach them to the connector.
1]
Peel approximately 40 mm of the coating off the end of the cable.
2]
Loosen and remove the mesh of the shielding. There are two signal lines, two power supply lines, and a
drain line inside the shielding.
3]
Peel off the aluminum tape wrapping the signal and power supply lines, then strip off the signal lines
(coating color: white and blue) and power supply lines (coating color: red and black) according to the
solderless terminal.
13.5 How to Connect Communication Cables to Connectors
Do not perform the wiring until the cable has been attached to the clamp terminals.
It is recommended to use a thin cable, in case of multidrop connection.
Table 13.1 Applicable clamp terminals
Number of lines
Cable
1 2(Multidrop)
Signal line
TMEVTC 1.25-11
-
Thick
Cable
Power line
TMEVTC 2-11
-
Signal line
TMEVTC 0.3-9.5
TMEVTC 1.25-11
Thin
Cable
Power line
TMEVTC 0.3-9.5
TMCVTC 1.25-11
Table 13.2 Applicable clamp tools
Clamp terminal
Clamp tool
TMEVTC 0.3-9.5
NH-5,NH-32,NH-60
TMEVTC 1.25-11
NH-11,NH-32
TMEVTC 2-11
NH-12,NH-32
TMEVTC 3.5-11S
NH-13
<Contact>
Nichifu Co., Ltd. Tel 03-3452-7381 (Tokyo Sales Dept.)
Approx.40mm
Drain
Peel the coating