Chapter 2 Specifications
2.2 Functional
specifications
Functional specifications are shown in Table 2.2. The compact remote modules have remote functions almost equal to
remote modules (RIOH-TM/RIOH-TL) for H-200/250/252B/252C series and remote modules (RIOM-TM/RIOM-TL)
for EM/EM-II series.
The compact remote modules have communication-compatibility with the remote I/O for EM/EM-II and
H-200/250/252B/252C and the remote I/O MINI for current H-2002/1002/702/302, and you can use an existing cable.
Therefore, you do not need to rewire the cable in replacement from these series.
Table 2.2 Functional specifications
Item Specifications
Usable CPU
EH-CPU104A/208A/316A/516/548, EHV-CPU16/32/64/128
Remote master module: Maximum 4 units / CPU (I/O assignment: “Remote 2”)
Connection modules
Remote slave module: Maximum 8 units / Master
Number of I/O points
256 points/master (I/O assignment: “Remote 2”),
128 points/master (I/O assignment: “4W/4W”)
Refresh time
2.5ms/256 points (HS: ON), 5.4ms/256 points (HS: OFF)
Self-diagnosis
SRAM check, WDT check, Loop back check
Fallback operation
Available (Even if a slave module is failed or powered off, it is possible to continue
communication between a master module and other slave modules)
I/O assignment (Note 1)
Master: “Remote 2” or “4W/4W”, Slave: No assignment
Mountable module on slave
base (Note 2)
8-point, 16-point I/O module (I/O assignment is “X16” or “Y16”)
Dummy module (I/O assignment is “Empty 16”)
32-point/64-point module, analog I/O module, and high-performance module,
communication
modules,
etc. cannot be mounted on the slave base.
Functional specifications
Consumption current
EH-TRMME: Approximately 150mA, EH-TRMLE: Approximately 150mA
Transmission speed
768kbps
Transmission mode
Half-duplex serial transfer, frame synchronization
Insulation, modulation method
Trans insulation, bipolar pulse modulation
Transmission error check
Reverse double-transmission, time-out
Tra
nsmission
sp
ecifi
cat
ions
Error display
LED, special internal output
Connection mode
Multi-drop system
Between stations: 150m (0.3mm2) / 300m (0.75mm2)
Cable length
Total length: 150m (0.3mm2) / 300m (0.75mm2)
Error station processing
Slave station: Bypass system
Cable
Shielded twist-pair cable
Existing
0.3mm
2
cable: CO-SPEV-SB(A)-1P-0.3SQ (Terminator 100
Ω
)
0.75mm
2
cable: CO-EX-SX-1P-0.75SQ (Terminator 150
Ω
)
Recommended
cable
(made by
Hitachi cable)
New
0.3mm
2
cable: CO-SPEV-SB(A)-1P-0.3SQ LF (Terminator 100
Ω
)
0.75mm
2
cable: CO-EX-SX 2
×
0.75SQ LF (Terminator 150
Ω
)
Transmission lin
e
Applicable connector
BL3.5/6F attached (made by Weidmuller)
(Note 1) “Remote 2” is unavailable to EH-CPU104A/208A/316A. Always use “4W/4W” for these. There is no function for the
read I/O assignment and copy. Set I/O assignment for remote slave by a programming software.
(Note 2) Please refer to “2.5 Supporting module list in salve station” for detail.