Chapter 2 Specifications
2.4
Remote masters that can be connected to remote slave (EH-TRMLE)
Remote masters that can be connected to remote slave module (EH-TRMLE) are shown in Table 2.4.
Table 2.4 Master list that can be connected to remote slave module (EH-TRMLE)
Specifications
Series of
PLC
Product
name
Model
name
Mode
I/O
assignment
for master
Not using
image slot
Using image slot
Remarks
Input:
128points
REMOTE 2
I/O:
256points
Output:
128points
Total:
256points
Input:
64points
EH-150
Remote
master
EH-TRMME
Compatible
mode
4W/4W
I/O:
64points
Outputs:
64points
Total:
128points
Input:
352points
MODE 0
4W/4W
I/O:
352points
Output:
352points
Total:
704points
MODE 1
Y8W
Output:
128points
Not available
Input:
64points
MODE 2
4W/4W
I/O:
64points
Output:
64points
Total:
128points
Large H
Remote
I/O MINI
REM-MMH
MODE 3
X8W
Input:
128points
Not available
Input:
128points
H-200/250/
252B/252C
Remote
master
RIOH-TM -
REMOTE
I/O:
128points
Output:
128points
Total:
256points
Cease in
production
Input:
128points
EM/EM-II
Remote
master
RIOM-TM -
Unnecessary
I/O:
128points
Output:
128points
Total:
256points
Cease in
production
Input:
128points
HL-40DR -
REMOTE
I/O:
128points
Output:
128points
Total:
256points
Input:
128points
H board
type
Unit with
remote
function
HL-64DR -
REMOTE
I/O:
128points
Output:
128points
Total:
256points
Cease in
production
2 – 4