Chapter 3 Name and function of each part
3 – 4
3.2
Name and function of each part in slave module
Name and function of each part
Model name
EH-TRMLE
Weight
Approx. 0.14 kg
Consumption current (5VDC)
Approx. 150 mA
Dimensions (mm (in.))
1] Lock button
7] Communication
connector
3] Rotary switch
(upper)
2] LED display
4] Rotary switch
(lower)
6] Front DIP switch
5] Reset switch
45 (1.77)
95 (3.74)
100 (3.
94)
No. Name
Function
Remarks
1]
Lock button
This is used when removing the module from base unit. After it is
installed to the base unit, the fixation can be reinforced using screws.
In this case, use M4
×
10 mm (0.39 in.) screw.
2]
LED display
The status of module is displayed on this LED.
See a table
shown below
3]
Rotary switch (upper)
This is a switch to set the station No.
See next page
4]
Rotary switch (lower)
This is a switch to set the number of occupancy slots.
See next page
5]
Reset switch
The module can be reset by pressing this switch when error such as
the module abnormal occurred.
See Section 6.4
for details.
6]
Front DIP switch
This is a switch to set an operation mode (HS refresh mode, etc.).
See next page
7]
Communication connector
This is a connector to connect a twist-pair cable for communication.
See next page
or later.
8]
Bottom DIP switch
This is a switch to set an operation mode (the first slave number of
slave, etc.).
See next page
or later.
Description of LED display
LED
LED
name
Indication Details
POW Power supply
Light up when 5V DC power is supplied to the module.
RUN
Normal
communication
Light up in proper communication. (Light is turned off due to
time-out error when the communication with slave station is
discontinued for 500ms or more.)
TxD
Transmission data Light up according to transmission data from slave station.
RxD
Received data
Light up according to received data from master station.
HERR Hardware error
Light up when hardware failure in master module is detected.
RUN
RxD
HERR CERR
POW
TxD
REMOTE
EH-TRMLE
CERR
Communication
error
Light up during communication error. (Light is turned off
automatically when communication is recovered.)
8] Bottom DIP switch