Chapter 4 Basic functions and System configuration
4 – 19
Figure 4.27 Example of I/O assignment for slave bases (with Control editor in system configuration example-12)
Figure 4.28 Replaced system configuration example-12 of the EH-150
Occupied channels of master No.1
Input
Output
0
X10000
~
X10015
-
1
X10100
~
X10115
-
2
X10200
~
X10215
-
3
X10300
~
X10315
-
4
X10400
~
X10415
-
5
X11000
~
X11015
-
6
X11100
~
X11115
-
7
X11200
~
X11215
-
Channel
No.
Setting of master No.1
A
U
I/O
assignment:
A
(Remote 2)
2
L
Number of
slaves:
2
8
ON
3 4
6 7
2
1
5
Compression
mode:
OFF
Final CH:
7
Setting of slave St. No.0
0
U
Slave St. No.:
0
5
L
Number of
occupied
slots:
5
8
3 4
5 6
2
1
ON
7
Compression
mode:
OFF
First CH:
0
Setting of slave St. No.1
1
U
Slave St. No.:
1
3
L
Number of
occupied
slots:
3
8
3 4
5 6
2
1
ON
7
Compression
mode:
OFF
First CH:
5
Master module
(EH-TRMME)
Slave module
(EH-TRMLE)
Slave module
(EH-TRMLE)
X
16
X
16
X
16
X
16
X
16
X
16
Occupied channels of slave St. No.1
Input
Output
5
X11000
~
X11015
-
6
X11100
~
X11115
-
7
X11200
~
X11215
-
Channel
No.
Occupied channels of slave St.No.0
Input
Output
0
X10000
~
X10015
-
1
X10100
~
X10115
-
2
X10200
~
X10215
-
3
X10300
~
X10315
-
4
X10400
~
X10415
-
Channel
No.
X
16
X