Chapter 6 Error indication and Countermeasure
6.2
Special internal outputs in CPU module
Remote refresh time and information about time-out error are stored in special internal outputs as shown in Table
6.3 when I/O assignment of master module of compact remote is “REMOTE 2”.
Please note that the information to be stored is different from the other remote system. And pay attention that these
information are not stored when I/O assignment of master module is “Word 4W/4W”.
■
Special internal outputs number of each master
Master No.1: WRF080
~
WRF097
Master No.2: WRF098
~
WRF0AF
Master No.3: WRF0B0
~
WRF0C7
Master No.4: WRF0C8
~
WRF0DF
Table 6.3 Special internal outputs concerning with remote in CPU module
Special internal outputs number
Contents of each bit number
Master
No.1
Master
No.2
Master
No.3
Master
No.4
Name
15
14
8 7
0
WRF080
WRF098
WRF0B0
WRF0C8
Assignment flag of slave
Bit number correspond to slave station number
(1: slave is assigned, 0: slave is not assigned)
WRF081
WRF099
WRF0B1
WRF0C9
Undefined
0
WRF082
WRF09A
WRF0B2
WRF0CA
Undefined
0
WRF083 WRF09B WRF0B3
WRF0CB
Detail information of transmission
error in slave ST. No.0 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF084 WRF09C WRF0B4
WRF0CC
Detail information of transmission
error in slave ST. No.1 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF085 WRF09D WRF0B5
WRF0CD
Detail information of transmission
error in slave ST. No.2 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF086 WRF09E WRF0B6
WRF0CE
Detail information of transmission
error in slave ST. No.3 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF087 WRF09F WRF0B7
WRF0CF
Detail information of transmission
error in slave ST. No.4 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF088 WRF0A0 WRF0B8
WRF0D0
Detail information of transmission
error in slave ST. No.5 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF089 WRF0A1 WRF0B9
WRF0D1
Detail information of transmission
error in slave ST. No.6 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF08A WRF0A2 WRF0BA
WRF0D2
Detail information of transmission
error in slave ST. No.7 (Note 1)
k
Error channel No.
Number of times
transmission error
WRF08B
WRF0A3
WRF0BB
WRF0D3
Detail information of transmission
error in slave ST. No.8 (Note 1)
0
~
~
~
~
~
~
WRF092
WRF0AA
WRF0C2
WRF0DA
Detail information of transmission
error in slave ST. No.15 (Note 1)
0
WRF093
WRF0AB
WRF0C3
WRF0DB
I/O verify mismatch slot No.
0
WRF094
WRF0AC
WRF0C4
WRF0DC
I/O error slot No.
0
WRF095 WRF0AD WRF0C5
WRF0DD
Refresh time (Maximum)
Remote refresh time (Maximum) (unit: ms)
WRF096 WRF0AE WRF0C6
WRF0DE
Refresh time (Minimum)
Remote refresh time (Minimum) (unit: ms)
WRF097 WRF0AF WRF0C7
WRF0DF
Refresh time (Current)
Remote refresh time (Current) (unit: ms)
(Note 1) The transmission error in slave is time-out error detected when there is no response about same cannel from slave station
during 0.5 ms. And following information are stored in each bit.
k: 1 is set when time-out error is detected. Because it is not cleared even if the communication recovers, you can
know the presence of past error.
Error channel No.: Channel No. of the time-out error detected at the end is stored.
Number of times transmission error: The number of errors of the accumulation after the power supply on base unit
is turned on is stored. It returns to 0 when it exceeds to 255, and count is continued.
These error information are cleared by turning on again the power supply. Please note that these error information are not
cleared by pushing the reset switch in master module and slave module.
6 – 2