Chapter 6 Error indication and Countermeasure
(3)
CERR LED of master module lights. (transmission time-out error)
Or, remote I/O doesn't operate.
CERR LED of master
module lights.
Y
Please exchange the remote module.
It happened many
times.
Connection of cables
is correct.
Y
It is thought the temporary one by the
noise. Please investigate, and confirm the
noise source.
N
Turn on the power supply of slave station.
N
Set rotary switch and DIP switch of master
and slave correctly.
Refer to Chapter 3 for details.
Y
N
Y
Setting of switches of master
and slave is correct.
I/O assignment and I/O numbers
in program is correct.
N
Power supply of slave is
turning on.
Setting of termination
is correct.
Y
Y
Shielded twisted pair
cable is recommended
cable.
Y
Set DIP switch in order to insert correct
value of resister for terminator in both
ends of master or slave modules connected
in transmission line.
N
Please connect the cable correctly.
Y
Check slave module indicated
transmission error with special internal
output.
Use recommended cable for shielded
twisted pair cable. Refer to Table 2.2 for
recommended cables.
N
N
The slave indicated error.
(Note 1)
(Note 1) You can know the slave ST. No. where
time-out error occurs by checking special internal
output as shown in Table 6.3. (in the case of I/O
assignment of master module is “REMOTE 2”)
Set I/O assignment and I/O numbers in
program correctly.
N
6 – 7