Chapter 6 Error indication and Countermeasure
(4)
CERR LED of slave module lights. (transmission time-out error)
Y
N
LED continues on after 30
seconds.
CERR LED of master
module lights.
Y
It is thought the temporary one by the
noise. Please investigate, and confirm the
noise source.
Setting of termination
is correct.
Connection of cables
is correct.
N
Y
Setting of switches of master
and slave is correct.
N
N
Turn on the power supply of master
station.
It happened many
times.
Power supply of master is
turning on.
N
Set I/O assignment and I/O numbers in
program correctly.
Y
Y
I/O assignment and I/O numbers
in program is correct.
But communication error (CERR) of slave
module lights while master can’t start
communication after initial processing.
Refer to Section 5.4 for detail.
Set rotary switch and DIP switch of master
and slave correctly.
Refer to Chapter 3 for details.
N
Y
Please connect the cable correctly.
N
Y
Shielded twisted pair
cable is recommended
cable.
Y
Set DIP switch in order to insert correct
value of resister for terminator in both
ends of master or slave modules connected
in transmission line.
N
Use recommended cable for shielded
twisted pair cable. Refer to Table 2.2 for
recommended cables.
Please exchange the remote module.
6 – 8