Chapter 5 Instruction specifications
5-123
(6)
"t" parameter
: Set by user
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[A]
[B]
t
t+B
[0] Execution bit:
Set "1" by user program to send data. This bit is reset after communication completed.
[1] Communication completed :
This bit is set "1" when communication completed without error, and reset at communication starting.
[2]
Communication failed :
This bit is set "1" when communication fails, and reset at communication starting.
[3] Initialize :
Set "1" by user program to initialize RECV 0 command. If this bit is on while communication, the communication
is forced to be stopped.
[4] Initialize completed :
This bit is set "1" when initializing completed without error. Initialize bit [3] is reset at this timing.
[5] Send enabled :
Set "1" by user program if CPU needs to send data after data receiving. This bit is reset after communication
completed.
[6] Parity error flag :
This bit is set "1" when parity error detected.
[7] Framing error :
This bit is set "1" when framing error detected.
[8] Overrun error :
This bit is set "1" when overrun error detected.
[9] Timeout :
This bit is set "1" when timeout detected.
[A] Input buffer full :
This bit is set "1" when input buffer full
[B] Conflict error :
This bit is set "1" when TRNS 0 or RECV 0 commands are duplicated.
Bit [6] to [B] is reset at initializing and RECV 0 executed.
(7) Sending/receiving data format (See TRNS 0 command)
Caution
z
Be sure to switch port type at first from dedicated port to general purpose port by FUN 5 command in user program.
z
If CPU receives data by RECV command after data sending, sent data could be failed depending on timing. In such a case,
RECV command with "send enabled" is recommended.
z
No contact nor condition is allowed to use with RECV 0 command.
z
Be sure to set [0] Execution bit high in 2
nd
scan or later. (Not in 1
st
scan)
z
If parameter setting is wrong, error code H52 (TRNS/RECV command error) is set in WRF000 in some cases.
z
ER signal is set on in the following condition.
Communication executed properly.
z
ER signal is set off in the following condition.
-
Initialized bit being set "1" while communication.
-
CPU status changed RUN
→
STOP
→
RUN while communication
-
Timeout while communication.
-
s, t parameters overwritten and range error while communication.
R
E
C
V
0
(
d, s, t)
Summary of Contents for HIDIC MICRO-EH
Page 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Page 12: ...MEMO ...
Page 14: ...Chapter 1 Features 1 2 MEMO ...
Page 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Page 196: ...Chapter 5 Instruction Specifications 5 146 ...
Page 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...