Chapter 3 Function and Performance Specifications
3-11
(6) Relay output
Item
Specification
Circuit diagram
Rated load voltage
5 to 250 V AC, 5 to 30 V DC
Minimum switching current
1 mA
1 circuit
2 A (24 V DC, 240 V AC)
Maximum
load current
1 common
5 A
OFF
→
ON
15 ms (max)
Output
response time ON
→
OFF
15 ms (max)
Number of output points
See Chapter 4.
Number of common
See Chapter 4.
Surge removing circuit
None
Fuse
None
Insulation system
Relay insulation
Output display
LED (green)
External connection
Removable type screw terminal block (M3)
Externally supplied power
(for driving the relays)
Not necessary
Contact life *1
20,000,000 times (mechanical)
200,000 times (electrical: 2 A)
Insulation
1500 V or more (external-internal)
500 V or more (external-external)
*1:
Refer to the Life curve of relay contacts in Chapter 10 for the details.
(7) AC output (SSR)
Item
Specification
Circuit diagram
Output specification
Triac output
Rated voltage
100/240 V AC
Output voltage
100 –15 % to 240 +10 % V AC
50 –5 % to 60 +5 % Hz
1 circuit
0.5 A 240 V AC
Maximum
load current
1 common
2 A
Minimum load current
100 mA
Maximum leakage current
1.8 mA 115 V AC(max)
3.5 mA 230 V AC(max)
Maximum inrush current
5 A (at 1 cycle or less)/point
10 A (at 1 cycle or less)/common
Off
→
On
1 ms or less
Maximum
delay time
On
→
Off
1 ms + 1/2 cycle or less
Output common
See Chapter 4.
Polarity
See Chapter 4.
Insulation system
Phototriac insulation
Fuse *2
Used
Surge removing circuit
Sunabar c varistor
External connection
Removable terminal block
Voltage drop
1.5 V RMS (max)
Insulation
1500 V or more (external-internal)
500 V or more (external-external)
*2:
It is necessary to repair the module if the load short-circuits and causes the fuse to melt.
Note that the fuse cannot be replaced by users.
0
1
C
In
tern
al circu
it
0
1
C
In
tern
al circu
it
Summary of Contents for HIDIC MICRO-EH
Page 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Page 12: ...MEMO ...
Page 14: ...Chapter 1 Features 1 2 MEMO ...
Page 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Page 196: ...Chapter 5 Instruction Specifications 5 146 ...
Page 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...