Chapter 5 Instruction Specifications
5-33
Program description
[Time chart]
X00005
CL15
CU15
1
2
3
4
5
65 535
3
Progress
value of
CU15 (TC15)
1]
2]
4]
Set value 4
5]
3]
Ignored
Ignored
1] The progress value (count) is cleared to 0 by the counter
clear (CL15). While the counter clear is on, the progress
value will not be updated.
2] The progress value is updated at the leading edge of
X00005.
3] Counter coil (CU15) is turned on since the progress value
≥
set value.
4] The count value will not exceed 65535 (decimal).
5] The progress value and counter coil are cleared by counter
clear (CL15).
•
The clear is performed under the conditions set immediately
prior to the execution of the counter coil instruction.
•
Example using word I/O as the set value
When RUN is commenced, the set value is set to the word I/O.
Or, the word I/O for the set value is designated to store in the power failure memory.
O
U
T
CU
n
s
Summary of Contents for HIDIC MICRO-EH
Page 1: ...HITACHI PROGRAMMABLE CONTROLLER APPLICATION MANUAL NJI 350B X ...
Page 12: ...MEMO ...
Page 14: ...Chapter 1 Features 1 2 MEMO ...
Page 50: ...Chapter 4 Product lineup and wiring 4 18 MEMO ...
Page 196: ...Chapter 5 Instruction Specifications 5 146 ...
Page 263: ...Chapter 11 Communication Specifications 11 10 MEMO ...