H E A T P U M P W A T E R H E A T E R C O M P R E S S O R C R I T E R I A
PAGE:8/30
8 Discharge pipe temperature
Discharge pipe temperature is measured at a distance 300mm from the surface of compressor
and should be less than 110℃. The tip of the thermocouple is fixed by soldering when
measuring discharge pipe temperature .Furthermore, soldering point is covered with urethane
foam to prevent the effect of wind.
9 Dust of compressor hermetic terminals
Compressor hermetic terminals should be mounted with specified cover in right way to prevent
dust entering, and should be used in direction which dust is hard to enter in.
10 Lead wire of compressor hermetic terminals
Measuring the temperature of hermetic terminals , lead wire should be resist to the temperature
and be clamped so as not in touch with the surface of compressor and pipe.
11 Start-stop frequency
The frequency should be less than 6 times per hour. Operating time from start to stop should
be more than 3 minutes. Stopping time should be more than 3minutes.
。
12 Rate of rotational speed change
The rate of compressor rotational speed (acceleration) should be less than 133min
-1
/s, But if
The variable range is below 120min
-1
, rate can also be less than 600min
-1
when rotational
speed is reduced to avoid temporary over- current.
13 Air and moisture in refrigerating system
The degree of vacuum in refrigerating system should be less than 20Pa (150×10
-3
mmHg) at
room temperature just before charging refrigerant. The quantity of water should be less
than 0.15ml.
Summary of Contents for Highly WHP11500VSD
Page 8: ...Arbeitsbereich siehe Bild 1 20 C A ...
Page 19: ...17 30 ...
Page 20: ...18 30 ...
Page 21: ... 19 30 ...
Page 22: ...20 30 ...
Page 23: ...21 30 ...
Page 24: ...22 30 ...
Page 25: ...23 30 ...
Page 26: ...24 30 ...
Page 27: ...25 30 ...
Page 28: ...26 30 ...
Page 30: ...28 30 ...
Page 31: ...CHART 3 Instructions forInverter rotary compressor revolutions change 29 30 ...