H E A T P U M P W A T E R H E A T E R C O M P R E S S O R C R I T E R I A
PAGE:7/31
G
raph 1 图 1
P1
P2
P3
P4
P5
P6
P7
P8
Condensing temperature
70℃
25℃
10℃
10℃
65
℃
80
℃
80
℃
80
℃
Evaporation Temperature
25℃
25℃
10℃
-35℃
-35
℃
-10
℃
-5
℃
15
℃
*Requirement for high pressure ratio condition can be seen on page 28.
6 Current limitation
Current peak among motor terminals(include instantaneous current peak)should be
below d
emagnetizing current
in order to prevent magnet in motor from demagnetization.
7 Pressure difference between suction and discharge 吸气、排气压力差
In all allowable rotational speed range, the difference of pressure should be more than
0.39MPa{4kgf/cm
2
}. But if there is no problem of noise when assembled in air conditioner,
it can also below this value(the requirement can be seen on page 28).
8 Discharge pipe temperature
Discharge pipe temperature is measured at a distance 300mm from the surface of compressor
and should be less than 110℃. The tip of the thermocouple is fixed by soldering when
measuring discharge pipe temperature .Furthermore, soldering point is covered with urethane
foam to prevent the effect of wind.